Home  /  Glossary  /  What is a single-phase supply?

Business Energy Glossary

What is a single-phase supply?

A single-phase supply is the basic UK electricity supply configuration. Power is delivered through one live conductor and one neutral, at a nominal voltage of 230 V. Single-phase is the standard for domestic premises, small offices, retail units, and any commercial site with modest power requirements. The maximum capacity of a typical single-phase supply is around 23 kW (100 A at 230 V), beyond which a three-phase supply is required.

Single-phase covers the majority of UK electricity supplies by count but only a smaller share of total consumption. Most commercial sites with significant equipment, multiple appliances running simultaneously, or any three-phase equipment will need to upgrade to three-phase. Understanding the limits of single-phase is essential when planning new equipment installations or business expansion.

How single-phase works

A single-phase electricity supply delivers power through one alternating current waveform, varying at 50 Hz. The supply consists of three conductors: one live carrying the AC waveform, one neutral providing the return path, and one earth for protective grounding.

The nominal voltage between live and neutral is 230 V in the UK. The actual voltage may vary within a permitted range (+10/-6 per cent under BS EN 50160), so the supply could measure anywhere from 216 V to 253 V at any given moment.

Capacity of a single-phase supply

The capacity of a single-phase supply is determined by the rating of the cut-out fuse installed by the DNO. Standard ratings:

Cut-out fuse ratingMaximum powerTypical use
60 A~13.8 kWOlder domestic, small flats
80 A~18.4 kWLarger domestic, very small commercial
100 A~23.0 kWStandard new commercial single-phase

The maximum power assumes the supply runs at full capacity continuously, which is rare. In practice the supply can handle short-duration peaks above the nominal rating but the long-term average must stay within the cut-out fuse limit. Sustained over-current trips the fuse and disconnects the supply.

When single-phase is suitable

Single-phase is sufficient for any commercial site where:

  • Peak demand stays comfortably below 100 A (around 23 kW).
  • No equipment requires three-phase power (most lighting, sockets, small appliances are single-phase).
  • No high-power motors, large air conditioning units, or rapid EV chargers are present.
  • The site is unlikely to expand its electrical load significantly.

Typical single-phase commercial sites: small offices, retail units, salons, takeaways, small cafes, and most retail high-street businesses.

Limits of single-phase

A single-phase supply hits its limits at three points:

  • Total simultaneous load. Multiple high-power appliances running at the same time (kettles, ovens, air conditioning, dishwashers) can exceed the cut-out rating, particularly on 60 A or 80 A supplies.
  • Three-phase equipment. Large air conditioning, commercial refrigeration, lifts, industrial motors, and rapid EV chargers above 7 kW require three-phase power. They cannot be operated on single-phase.
  • Network voltage drops. Long single-phase runs can have significant voltage drop under load. Three-phase distributes the load across three conductors, reducing the drop for the same total power.

Cost of a single-phase supply

Single-phase supplies have lower fixed costs than three-phase:

  • Lower standing charge. Single-phase meters and connections cost less to install and maintain.
  • Lower meter operation fee. Single-phase MOP and DC fees are typically half of equivalent three-phase fees.
  • Lower new connection charge. Where a new supply is being installed, single-phase is significantly cheaper than three-phase.

The unit rate per kWh is generally the same on single-phase and three-phase contracts. Energy consumed costs the same per kWh; the fixed elements differ.

Upgrading to three-phase

If the site outgrows its single-phase supply, an upgrade to three-phase is required. The process:

  1. Apply to the DNO through the supplier or directly. Specify the new capacity required in kVA.
  2. Receive a quotation covering the connection work, any network reinforcement, and the new meter installation.
  3. Accept and pay. Typical lead time: 4 to 12 weeks for urban sites, longer for rural sites needing reinforcement.
  4. Civil works completed by the DNO. Internal wiring upgrade is the customer responsibility.
  5. New three-phase meter installed by the supplier-appointed MOP. Supply energised.

Cost ranges from a few thousand pounds for a simple urban upgrade to tens of thousands for rural sites requiring substantial new infrastructure. The standing charge on the new three-phase supply will be higher than the previous single-phase, reflecting the more complex connection.

a single-phase supply FAQs

What is a single-phase electricity supply?

The basic UK electricity supply with one live conductor and one neutral, delivering 230 V at the customer side. Standard for homes and small commercial premises with modest power requirements.

How much power can a single-phase supply deliver?

Up to around 23 kW (100 A at 230 V) for the standard new commercial single-phase. Older supplies with 60 A or 80 A cut-outs deliver less (around 14 to 18 kW).

When do I need to upgrade to three-phase?

When peak demand exceeds the single-phase capacity, when three-phase equipment is being installed (large air conditioning, industrial motors, rapid EV chargers above 7 kW), or when expansion is planned that will exceed single-phase limits.

How do I know if I have a single-phase or three-phase supply?

Look at the meter and the cut-out at the supply intake. A single-phase supply has one live conductor entering the meter. A three-phase supply has three. The supplier can also confirm based on the MPAN profile class.

Is a single-phase supply cheaper than three-phase?

Yes on standing charge and meter operation fees. The unit rate per kWh is generally the same. New connections and upgrades cost less for single-phase than for three-phase.

Can a single-phase supply run three-phase equipment?

No. Three-phase equipment requires three live conductors offset by 120 degrees. A single-phase supply cannot provide this. The site would need to upgrade to three-phase or use single-phase equipment instead.

What voltage is a UK single-phase supply?

230 V nominal, with a permitted range of +10/-6 per cent under BS EN 50160. The actual voltage can vary from around 216 V to 253 V at any given moment.

Can I run a small EV charger on single-phase?

Yes for chargers up to 7 kW (32 A). Larger chargers (22 kW and above) require three-phase. A 7 kW charger fits comfortably within a 100 A single-phase supply if no other significant loads are running at the same time.

Clearsight Energy
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.